Tel:+86-755-27465585
Fax:+86-755-27270662
Email: sales@huaandz.com
Website: www.huaandz.com
Add:5F,Building C,No.30,Aviation Road,SanWei,XiXiang Street,BaoAn District,ShenZhen,China
AC Power line L-N applications
Class I and Class II Surge protection
Voltage : 800V
Up: <2000V
Uc: 320V
In: 25KA
Iimp: 25KA
Imax: 50KA
If: 500A
Specification of H6R20-800L | ||
Nominal Dc spark-over voltage @ 100V/s | A-B >600V | |
A-C >600V | ||
Maximum impulse spark-over voltage @ 1KV/μs | A-B <1200V | |
A-C(Add MOV) <1500V | ||
Response time | 50ns | |
Insulation resistance @250V | 1GΩ | |
Class I according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Impulse current 10/350μs Iimp Follow Current at 50/60Hz at 320V If |
320V 25KA 25KA 500A | |
Class II according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Maximum discharge current 8/20μs Imax Follow Current at 50/60Hz at 320V If |
320V 25KA 50KA 500A | |
Weight | ~ 36g | |
Delivery time | 25days | |
Voltage protection level | <2KV | |
Quantity of electric charge | 7.5As | |
Quantity of electrodes | 6PCS | |
Marking, Green
| 800 YY | 800 - Nominal voltage YY - Year of production |