Tel:+86-755-27465585
Fax:+86-755-27270662
Email: sales@huaandz.com
Website: www.huaandz.com
Add:5F,Building C,No.30,Aviation Road,SanWei,XiXiang Street,BaoAn District,ShenZhen,China
AC Power line N-PE applications
Class I and Class II Surge protection
Voltage : 600V
Up: <1200V
Uc: 260V
In: 20KA
Iimp: 8KA
Imax: 40KA
Specification of H2R16-600xx | ||
Dc spark-over voltage (100V/s) 1) | 600V ±20% | |
Maximum impulse spark-over voltage 1KV/μs | 1200V | |
Breakdown time - typical values | <100ns <20ns | |
Insulation resistance @DC250V | 1000MΩ | |
Class I according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Impulse current 10/350μs Iimp |
260V 20KA 8KA | |
Class II according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Maximum discharge current 8/20μs Imax |
260V 20KA 40KA | |
capacitance at 1MHz | <5pF | |
Weight | ~ 5g | |
UL 1449 Certification On the UL List |
| |
Delivery time | 20days | |
Operation and storage temperature | -40℃ … +90℃ | |
Marking, Blue 1) At delivery AQL 0.65 level II Military Standard 105E. 2) In ionized mode Test according to IEC 61643 11 ITU-T Rec. K.12 | 2R600 YY | 600 - Nominal voltage YY - Year of production |