Class I and Class II Surge protection
Voltage : 600V
Up: <1500V
Uc: 255V
In: 50KA
Iimp: 40KA
Imax: 100KA
If: 100A
TOV: 300A
Specification of 2B600D |
||
Dc spark-over voltage (100V/s) |
600V ±20% |
|
Front of wave spark-over voltage at 1.2/50us, 6KV |
<1500V |
|
Breakdown time - typical values |
<100ns <20ns |
|
Insulation resistance @DC250V |
>1*109 Ω |
|
Class I according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Impulse current 10/350μs Iimp Follow Current at 50/60Hz at 255V If |
255V 50KA 40KA 100A |
|
Class II according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Maximum discharge current 8/20μs Imax Follow Current at 50/60Hz at 255V If |
255V 50KA 100KA 100A |
|
AC discharge current (TOV at 1200V ,1 operation 50Hz,0.2 s) |
<300A |
|
capacitance at 1MHz |
<4pF |
|
Weight |
~ 38g /PCS |
|
Delivery time |
12days |
|
Operation and storage temperature |
-40℃ … +90℃ |
|
Marking, Red 1) At delivery AQL 0.65 level II Military Standard 105E. Approvals/ Standards IEC61643-11 |
600 YY |
600 - Nominal voltage YY - Year of production |