Tel:+86-755-27465585
Fax:+86-755-27270662
Email:sales@huaandz.com
Website:www.huaandz.com
Add:5F,Building C,No.30,Aviation Road,SanWei,XiXiang Street,BaoAn District,ShenZhen,China
Your Current Location >Home > Products > Gas Discharge Tubes > Φ18x6.7mm - 4C800
Φ18x6.7mm - 4C800

Φ18x6.7mm - 4C800

AC Power line N-PE applications

Class I and Class II Surge protection

Voltage : 800V

Up: <1500V

Uc: 255V

In:  40KA 

Iimp: 12.5KA

Imax: 65KA

If: 100A

TOV: 100A


Specification of  4C800

Dc spark-over voltage (100V/s)

800V  ±20%

Front of wave spark-over voltage at 1.2/50us, 6KV

1500V

Breakdown time   

           - typical values

100ns

20ns

Insulation resistance @DC250V

  >1*109 Ω

Class I  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μ                     In

Impulse current 10/350μ                             Iimp

Follow Current at 50/60Hz at 255V                      If

 

255V

40KA

12.5KA

100A

Class II  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μ                     In

Maximum discharge current 8/20μ                    Imax

Follow Current at 50/60Hz at 255V                       If

 

255V

40KA

65KA

100A

AC discharge current (TOV at 1200V ,1 operation 50Hz,0.2 s)

100A

capacitance at 1MHz

4pF

Weight

7g /PCS

Delivery time

14days

Operation and storage temperature

-40 … +90

Marking, Red

1) At delivery AQL 0.65 level II Military Standard 105E.

   Approvals/ Standards   IEC61643-11

800 

800 - Nominal voltage