AC Power line L-N applications
Class I and Class II Surge protection
Voltage : 800V
Up: <2000V
Uc: 380V
In: 50KA
Iimp: 30KA
Imax: 100KA
If: 1000A
Specification of H4R30-800L |
||
Nominal Dc spark-over voltage @ 100V/s |
A-B >300V |
|
B-C >800V |
||
C-D >300V |
||
A-D >1000V |
||
Maximum impulse spark-over voltage @ 1KV/μs |
A-B <1000V |
|
B-C <2800V |
||
C-D <1000V |
||
A-D <3000V |
||
Response time |
50ns |
|
Insulation resistance @250V |
1GΩ |
|
Class I according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Impulse current 10/350μs Iimp Follow Current at 50/60Hz at 380V If |
380V 50KA 30KA 1000A |
|
Class II according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Maximum discharge current 8/20μs Imax Follow Current at 50/60Hz at 380V If |
380V 50KA 100KA 1000A |
|
Weight |
~ 86g |
|
Delivery time |
25days |
|
Voltage protection level |
<2KV |
|
Quantity of electric charge |
17.5As |
|
Quantity of electrodes |
4PCS |
|
Marking, Green
|
R 800 YY |
800 - Nominal voltage YY - Year of production |