AC Power line L-N applications
Class I and Class II Surge protection
Voltage : 800V
Up: <2000V
Uc: 320V
In: 25KA
Iimp: 25KA
Imax: 50KA
If: 500A
Specification of H6R20S-800L |
||
Nominal Dc spark-over voltage @ 100V/s |
A-B >600V |
|
A-C >600V |
||
Maximum impulse spark-over voltage @ 1.2/50μs |
A-B <1200V |
|
A-C(Add MOV) <1500V |
||
Response time |
50ns |
|
Insulation resistance @250V |
1GΩ |
|
Class I according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Impulse current 10/350μs Iimp Follow Current at 50/60Hz at 320V If |
320V 25KA 25KA 500A |
|
Class II according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Maximum discharge current 8/20μs Imax Follow Current at 50/60Hz at 320V If |
320V 25KA 50KA 500A |
|
Weight |
~ 27g |
|
Delivery time |
25days |
|
Voltage protection level |
<2KV |
|
Quantity of electric charge |
7.5As |
|
Quantity of electrodes |
6PCS |
|
Marking, Green
|
800 YY |
800 - Nominal voltage YY - Year of production |