AC Power line N-PE applications
Class I and Class II Surge protection
Voltage : 800V
Up: <1500V
Uc: 264V
In: 40KA
Iimp: 12.5KA
Imax: 80KA
If: 100A
TOV: 300A
Specification of H2R20-800xx |
||
Dc spark-over voltage (100V/s) 1) |
>600V |
|
Front of wave spark-over voltage at 1.2/50us, 6KV |
<1500V |
|
Breakdown time - typical values |
<100ns <40ns |
|
Insulation resistance @DC250V |
1000MΩ |
|
Class I according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Impulse current 10/350μs Iimp Follow Current at 50/60Hz at 264V If |
264V 40KA 12.5KA 100A |
|
Class II according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Maximum discharge current 8/20μs Imax Follow Current at 50/60Hz at 264V If |
264V 40KA 80KA 100A |
|
AC discharge current (TOV at 1200V ,1 operation 50Hz,0.2 s) |
<300A |
|
capacitance at 1MHz |
<5pF |
|
Weight |
~ 6g |
|
UL 1449 Certification On the UL List |
|
|
Delivery time |
20days |
|
Operation and storage temperature |
-40℃ … +90℃ |
|
Marking, Blue 1) At delivery AQL 0.65 level II Military Standard 105E. 2) In ionized mode Test according to ITU-T Rec. K.12. |
2R800 YY |
800 - Nominal voltage YY - Year of production |